65
Appendix
CKIN:XXX/ZZZ END
Trip Counter For DMP Wireless Check-in Test (WLS)
Displays the number of wireless zones that automatically communicate a supervision
check-in message.
• The number of zones that check in. (XXX in the example).
• The total number of wireless zones programmed for supervision that should check
in. (ZZZ in the example).
END - Select END to stop the Wireless Check-in Test. When the test ends or a 20-minute
time-out expires, normal wireless zone processing returns. If all transmitters check-in, both
numbers match within three (3) minutes. If a transmitter has multiple zones (1101, 1114,
etc.), all zones are included in the counts. Failed wireless zones display on the keypad.
TEST END WARNING
Test End Warning
When ve minutes remain on the 20 minute Walk Test timer, the keypad displays TEST
END WARNING. If no additional test zone trips occur, the test ends and a nal Sensor
Reset automatically occurs. The System Test End message is sent to the receiver along
with Verify and Fail messages for each zone under Walk Test. Faulted zones then display
on the keypad.
Note: Key fobs do not send failure messages in order to prevent functioning key fobs that
are not present at the time of the test from being reported as MISSING.
Failed Zones Display
For each zone that did not trip (failed), except key fobs, at least once during the Walk
Test, all keypads with matching Area Display programming display the zone name and
number and buzz for one second. Any selected (*FI *PN *SV) 24-hour zone that is faulted
at the end of the Walk Test displays a trouble condition for that zone regardless of the
message programmed for the open or short condition of the zone and a zone trouble is
sent to the receiver. Press the COMMAND key to display the next failed zone.
Note: For the Wireless Check-in Test, failed wireless zones display only on the keypad.
Zone Verify/Fail reports are not sent to the central station receiver for the wireless
check-in test.
Local Printer for Walk Test
When the Walk Test is completed, a Verify or Fail message for each zone tested prints to the local printer. The
Walk Test messages printing is enabled through Printer Reports programming.
Note: If ENHANCED ZONE TEST is selected as YES, the Verify messages are printed at the time the zone trip
occurs and not printed at the test end.
23.5 Keypad Speaker Operation
When using LCD Keypads, the panel provides distinct speaker tones from the keypad for Fire, Burglary, Zone
Monitor, and Prewarn events. The list below details the conditions under which the speaker is turned on and off
for each event.
Fire On - Fire zone alarm and Bell Output or Fire Bell Output is ON.
Off - Alarm Silence.
Burglary On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
Off - Alarm Silence.
Zone Monitor On - One time only when a monitored zone is tripped.
Off - After one tone.
Prewarn On - During Entry Delay.
Off - When Entry Delay expires.
23.6 Cross Zoning
Caution must be taken when cross zoning devices
to ensure that the Cross Zone Time is long enough
to allow an intruder to trip both devices before it
expires. A Cross Zone Time that is too short may
allow an intruder to trip the devices and allow only
a zone fault report be sent to the central station.
When a Cross Zoned zone trips a FAULT report is sent
to the SCS-1R Receiver. When two Cross Zoned zones
trip within the Cross Zone Time, both zones send
ALARM signals to the receiver. For example, if zones
1 and 2 are Cross Zoned zones, and only zone 1
trips, a FAULT report is sent to the receiver for zone
1. If zone 1 trips and zone 2 trips within the Cross
Zone Time, an ALARM report is sent to the receiver
for zone 1 and zone 2.
SOUTH LOBBY
ZONE: 10 -FAIL
Report Type Immediately Delayed
Alarm Y
Trouble Y
Restore Y
Opening Y
Closing Y
Bypass Y
Reset Y
Supervisory Y
Add Codes Y
Delete Codes Y
Change Codes Y
Permanent Schedule Change Y
Temporary Schedule Change Y
Door Access Y
Door Access Denied Y
Late to Close Y
Force Armed Zone Y