XR500 Series Programming Guide Digital Monitoring Products
1
IntroductIon
Introduction
1.1 Before you Begin
This guide provides programming information for the DMP XR500, XR500N, and XR500E panels. After this
Introduction, the remaining sections describe the functions of each programming menu item along with the
available options. Before starting to program, we recommend that you read through the contents of this
guide. The information contained here allows you to quickly learn the programming options and operational
capabilities of the XR500, XR500N, and XR500E panels.
In addition to this guide, you should also read and be familiar with the following XR500 Series documents:
• XR500 Series Installation Guide (LT-0681)
• XR500 Series Programming Sheet (LT-0678)
• XR100/XR500 Security Command
®
User’s Guide (LT-0683)
Internal Programmer
The panel contains all of its programming information in an on-board processor and does not require an external
programmer. You can perform all programming tasks through a 32-character DMP alphanumeric keypad set to
address one.
Programming Information Sheet
Included with each panel are the Programming Information Sheets. These list the various programming options
and available options for programming the panel. Before starting to program, we recommend you completely ll
out each sheet with the programming options you intend to enter into the panel.
Having completed programming sheets available before entering data helps prevent errors and can shorten the
time you spend programming. Completed sheets also provide you with an accurate panel program record you
can keep on le for future system service or expansion. The remainder of this Introduction provides instructions
for starting and ending a programming session using the alphanumeric keypad.
1.2 Getting Started
Ground Yourself Before Handling the Panel! Touch any grounded metal, such as the enclosure, before touching
the panel to discharge static.
Remove All Power From the Panel! Remove all AC and Battery power from the panel before installing or
connecting any modules, cards, or wires to the panel.
Before starting to program the XR500 Series panel, make sure the panel is properly grounded and AC and battery
power is applied to the appropriate panel terminals. All wiring connections and grounding instructions are
detailed in the XR500 Series Installation Guide (LT-0681).
Program from any Keypad Address or Wireless Keypad
You can program the XR500 panel from any 32-character wireless keypad or hardwired keypad connected to the
panel’s keypad data bus. See the XR500 Installation Guide for keypad addressing and installation information for
hardwired keypads.
Wireless Keypads can be used for panel programming after being programmed in the panel manually or by using
the Wireless Keypad Association operation.
To enable association operation in the keypad, access the Installer Options Menu (3577 (INST)) and select RF
Survey. The keypad logo LEDs turn on Red until association is successful.
To enable association operation in the XR500 panel, reset the panel 3 times within 12 seconds. Allow the panel’s
keypad bus Transmit/Receive LEDs to turn back on between each reset.
For 60 seconds the panel listens for wireless keypads that are in the Installer Options Menu and have not been
programmed, or associated into another panel. Those keypads are assigned to the rst open device position
automatically based upon the order in which they are detected. The keypad logo turns Green to indicate it
has been associated with the panel. See the 9000
Series Wireless Keypad Installation Guide (LT-1107) for
additional information.
Accessing the Programmer
1. Momentarily place the Reset jumper over both
of the J16 pins to reset the panel.
2. Enter the code 6653 (PROG) and press
COMMAND.
3. The keypad displays: PROGRAMMER.
J6
Interface
Card
Expansion
Connector
To enable Wireless Keypad
Association operation:
Reset panel 3 times within
12 seconds.
To access the programmer:
Momentarily place the
Reset jumper over both of
the J16 pins to reset the
panel.
AC
12345678 10 11 12 13 14 15 16 17 18 19
02122 23 24 25 26 27 28
+B BELL GND SMK GNDRED YEL GRN BLK Z1 Z2 Z3 Z4 Z5 Z6 Z7 Z8 Z9+ Z9– Z10+ Z10–AC –B GND GND GNDGND
K6 K7
Output 1 Output 2
J3
Phone Line
J10
J22
LX-Bus
Battery
Start
J23
J21
RS-232
Power
LED
J8
PROG
J4
Tamper
J16
Reset
Out1 Out2
Outputs 3-6
J11
3
4
5
6
J2
J1
Ethernet
R
L
X
OVC
Link LED
Activity LED
Figure 1: XR500 Series Panel Showing Reset
Comentarios a estos manuales