XR500 Series Programming Guide Digital Monitoring Products
39
StatuS LiSt
15.5
BURGLARY ZONES:
Burglary Zones
Species the keypad addresses (1 through 16) where all burglary zone alarms and
troubles display. Bur glary zones in clude Night, Day, and Exit type zones. Burglary zone
troubles remain in the list until the zone restores. All keypads are selected by default.
For zone alarms, only the last burglary zone tripped re mains in the list. The alarm re-
mains in the list un til another burglary zone goes into alarm, any area of the system is
dis armed, or 10 minutes elapse without an alarm. This ensures that if a bur glary is in
progress the last zone tripped remains in the list even if the zone is restored.
The keypad buzzer sounds for one second on bur glary alarms.
When using LCD Keypads, the panel provides distinct speaker tones from the keypad for
Burglary:
On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
Off - Alarm Silence.
You can further dene which keypad address shows a Burglary Zone event by entering
that area number in the Display Areas menu during Device Setup.
15.6
SPRVISORY ZONES:
Supervisory Zones
Species the keypad addresses (1 through 16) where all su pervisory zone alarms and
troubles display. Supervisory zones are entered in the sta tus list and sound the keypad
buzzer until a valid user code is entered at any keypad address. If a trouble condition
remains in the display, the buzzer sounds at 10:00 am daily until the supervisory trouble
is cleared from the Status List.
15.7
PANIC ZONES:
Panic Zones
Species the keypad addresses (1 through 16) where all panic zone alarms and troubles
display. The name of the zone remains in the list until the zone re stores. The keypad
buzzer does not sound for panic alarms or troubles.
15.8
EMERGENCY ZONES:
Emergency Zones
Species the keypad addresses (1 through 16) where all emer gency zone alarms and
troubles display. The name of the zone remains in the list until the zone re stores. The
keypad buzzer does not sound for emer gency alarms or troubles.
15.9
AUX 1 ZONES:
Auxiliary 1 Zones
Species the keypad addresses (1 through 16) where all Aux iliary 1 zone alarms and
troubles display. The name of the zone remains in the list until the zone restores. The
keypad buzzer does not sound for Auxiliary 1 alarms or troubles.
You can further dene which keypad address shows an Auxiliary 1 Zone event by entering
that area number in the Display Areas menu during Device Setup.
15.10
AUX 2 ZONES:
Auxiliary 2 Zones
Species the keypad addresses (1 through 16) where all Aux iliary 2 zone alarms and
troubles display. The name of the zone remains in the list until the zone restores. The
keypad buzzer does not sound for Auxiliary 2 alarms or troubles.
You can further dene which keypad address shows an Auxiliary 2 Zone event by entering
that area number in the Display Areas menu during Device Setup.
15.11
COMM PATH TRBL:
ALL NO YES
Communication Trouble
Species when communication troubles are displayed on keypads that are programmed to
display System Monitor Troubles. Default is NO.
Select YES to display communication trouble when any communication path fails.
Select ALL to display communication trouble only when all paths have failed.