XR500 Series Programming Guide Digital Monitoring Products
19
Device Setup
6.18.4
ACTIVATE ZONE 3
REX? NO YES
Activate Zone 3 Request to Exit
Selecting YES activates the Zone 3 Request to Exit (REX) option.
Selecting NO allows standard zone operation on Zone 3 and displays the ACTIVATE
ONBOARD SPEAKER option. Default setting is NO.
Optionally connect a PIR (or other motion sensing device) or a mechanical switch to Zone
3 to provide REX capability to the system. When Zone 3 shorts, the on-board Form C
relay activates for the programmed number of seconds. During this time, the user can
open the protected door to start the programmed Bypass entry/exit timer. After the
programmed number of seconds, the relay restores the door to its locked state.
The 734/734N/734N-WiFi module provides a bypass-only option for REX on Zone 3. When
Zone 3 opens from a normal state, only a bypass occurs: the on-board relay does not
activate. This bypass-only option uses two methods of REX. The rst REX device provides
the programmed Bypass entry/exit timer. The second REX device, or manual device such
as a door knob, unlocks the door.
An example of the bypass-only conguration is a door to an ofce that is locked 24 hours
a day. Users pass a REX motion detector positioned by the door to begin the programmed
exit timer. Within the programmed number of seconds the user must then manually
activate a second device, such as a REX device or manual door knob, to unlock the door. If
the door is opened after the programmed number of seconds, the zone goes into alarm.
6.18.5
ZN 3 REX STRIKE
TIME: 5
Zone 3 REX Strike Time
Enter the number of REX seconds to elapse. Range is from 5 to 250 seconds. Press any top
row select key to enter the number of seconds. The default is 5 seconds.
6.18.6
ACTIVATE ONBOARD
SPEAKER? NO YES
Activate Onboard Speaker
Select YES to enable the onboard piezo speaker for local annunciation. Select NO to turn
the piezo off for all operations. This does not affect remote annunciator open collector
(RA) operation. The default is NO.
6.18.7
CARD OPTIONS:
DMP
Card Options
Press any top row Select key to display options. Press the select key under DMP,
CUSTOM, or ANY to select that option. Select DMP to indicate the reader sends a 26-
bit DMP data string. Press the COMMAND key to display REQUIRE SITE CODE.
Note: When set to DMP, the 734/734N/734N-WiFi converts 17 bits of the 26-bit data
string into a 5-digit number.
Select CUSTOM if using a non-DMP card or user code length of 6 to 10 digits.
Default is DMP.
Select ANY to allow all card reads to activate the door strike relay. The door strike
relay is activated for the length of time programmed in ZN 3 REX STRIKE TIME. No user
code information is sent to the panel.
CustomCardDenitions
6.18.8 Weigand Code Length
When using a custom credential, enter the total number of bits to be received in
Wiegand code including parity bits.
Press any top row Select key to enter a number between 1-255 to equal the number of
bits. Default is 26 bits.
Typically, an access card contains data bits for a site code, a user code, and start/stop/
parity bits. The starting position location and code length must be determined and
programmed into the 734/734N/734N-WiFi Module.
CARD OPTIONS:
DMP CUSTOM ANY
WIEGAND CODE
LENGTH: 26
01110101101101010001100111
First Bit
Received
Position = 0
Site Code
Position = 1
Length = 8
User Code
Position = 9
Length = 16
Last Bit
Received
Position = 25
In this example the Wiegand Code Length = 26 bits.