XR500 Series Programming Guide Digital Monitoring Products
23
Remote options
7.9 Manufacturer Authorization
Select YES to allow DMP Technical Support technicians to access the panel during system
service or troubleshooting. This authorization automatically expires within one hour.
DMP remote service is provided on a read only basis: DMP technicians can look at the
system programming and make suggestions only. Alterations can only be accomplished by
installing company service personnel.
7.10 Allow Network Remote
This option displays only if the panel has network capability. YES allows remote
programming over the network. Changing this option does not change any other network
programming options. Default is YES.
7.10.1
NETWORK PROG
Network Programming Port
PORT: 2001
Enter the programming port number. The programming port identies the port used to
communicate messages from the panel. The default Programming Port setting is 2001.
7.10.2 Encrypt Network Remote
YES encrypts data sent over network. Default is NO.
7.11 Allow Cellular Remote
YES allows remote programming using cellular connection. Default is YES.
7.11.1 First GPRS APN
Enter the rst APN (Access Point Name). This allows an access point for cellular
communication and is used to connect to a DNS network. The APN may contain two lines
of 16 characters to equal 32 characters. Default is set to SECURECOM400.
Note: This option is not used when a 463C CDMA or 464-263C Cellular Communicator
is used for communication.
Second GPRS APN
Enter the second APN (Access Point Name). This works as a backup in case the rst APN
fails. The APN may contain two lines of 16 characters to equal 32 character Default is set
to SECURECOM400.
Note: This option is not used when a 463C CDMA or 464-263C Cellular Communicator
is used for communication.
7.11.2 Encrypt Cellular Remote
YES encrypts data sent over a cellular connection. Default is NO.
7.12 Allow RS-232 Remote
YES allows remote programming over the on-board RS-232 port. Default is YES.
7.13 Entré Connection
This option displays only if the panel has network capability. Select NET to allow a
dedicated network connection with Entré. Options are NONE or NET. Default is NONE.
7.13.1 Entré Incoming TCP Port
This option displays only if NET is chosen for the Entré connection. Enter the
programming port number for the incoming Entré connection. The programming port
identies the port used to communicate messages to and from the Entré software. This
port cannot be the same port as programmed in Network Programming Port. The default
Programming Port setting is 2011.
7.13.2 Entré IP Address
This option displays only if NET is chosen for the Entré connection. Enter the Entré IP
address where the panel sends network messages. The Entré IP Address must be unique
and cannot be duplicated on the network. Enter all 12 digits and leave out the periods.
For example, enter IP address 192.168.0.250 as 192168000250. The periods display
automatically. Default is 0.0.0.0
7.13.3 Entré Outbound TCP Port
This option displays only if NET is chosen for the Entré connection. Enter the programming
port number for the outbound Entré connection. The programming port identies the port
used to communicate messages to the Entré software. Default is
2001.
SECURECOM400
-
FIRST GPRS APN:
SECURECOM400
-
SECOND GPRS APN:
ENCRYPT NETWORK
REMOTE? NO YES
ALLOW CELL
REMOTE? NO YES
AUTH? NO YES
ALLOW NETWORK
REMOTE? NO YES
MANUFACTURER
ENCRYPT CELL
REMOTE? NO YES
ALLOW 232
REMOTE? NO YES
ENTRE
CONNECTION: NONE
ENTRE INCOMING
TCP PORT: 2011
000.000.000.000
ENTRE IP
ENTRE OUTBOUND
TCP PORT: 2001