Digital Monitoring Products XR500 Series Programming Guide
54
Zone InformatIon
19.11.11
OUTPUT ACTION:
yyy: XXXXXXXX
Output Action
This option allows you to dene the output action (STD, PLS, MOM, TGL, OFF) for
the selected output number. The default is Steady.
yyy = the name of the button being programmed (TOP, BTM, LFT, RGT).
xxxxxxxx = the currently dened output action.
OUTPUT ACTION?
STD PLS MOM TGL
STD (Steady) - The output is turned on and remains on.
PLS (Pulse) - The output alternates one second on and one second off.
The pulsing rate for a Model 716 relay attached to the LX-Bus is 1.6 seconds.
Note: Pulse is not available for key fob button output programmed D1 to D16 or G1
to G20.
MOM (Momentary) - The output is turned on only once for one second.
TGL (Toggle) - The output alternates between the on state and off state. Each
button press toggles the output state.
Note: Toggle is not available for key fob button output programmed G1 to G20.
OUTPUT ACTION?
OFF
OFF (Off) - The output is turned off. If programmed, the output was turned on by
some other means such as another button press, a zone action, or a schedule.
Note: When the output is assigned to PN/PN2 or EM/EM2 button action and is
turned on, the output turns off when any area is disarmed.
When the output action is steady, pulse or toggle and the output is turned on, the
output remains on until:
— the output cutoff time expires
— the output is reset from the keypad menu
— toggled off
19.11.12
NEXT ZONE NO YES
Next Zone
Select YES to return to the ZONE NO: - option to program a new zone. Select NO to
display the Alarm Action option.
Note: All wireless programming is stored in the XR500 Series panel. The 1100X Wireless Receiver obtains the
necessary programming information from the panel each time the receiver powers up, when the programmer
STOP routine is selected or the panel is reset. The receiver memory refresh takes up to 10 seconds to complete
depending on the number of wireless zones programmed and the Red LED remains on during this time. Normal
receiver operation is inhibited during the memory refresh period.
FA Series Wireless
For an FA Series Remote Wireless Receiver set the House Code to 99. See House Code programming in System
Options. Only zones 500 to 699 can be programmed as FA Series Wireless zones for maximum of 200 Wireless
Zones.
For a DMP 1100X Wireless Receiver see section 16.10.
19.12
ZONE INFORMATION
WIRELESS? NO YES
Wireless
Select YES to program a wireless zone connected to an FA Series FA400-DMP Remote
Wireless Receiver. Press the COMMAND key to continue with wireless programming.
19.12.1
CHECK IN TM: 60
Check-in Time
You can set wireless transmitters to check in automatically every 10, 30, or 60
seconds or not at all. To change the 60 second default, press any top row Select key
to display NONE 10 30 60. Select the check-in time you want for this zone.
Note: Refer to the Wireless Check-in and Supervision Time Denitions section of the
Appendix for supervision information.
19.12.2
INT CONT NO YES
Internal Contact
Select YES to use an internal contact on the wireless transmitter. Select NO to use an
external contact. When you select NO, the following two options display.
19.12.3
EOL NO YES
End-of-Line
Select YES to supervise an external contact connected to the wireless transmitter.
At the contact, install a 2.2k Ohm End-of-Line resistor in parallel for Normally Open
contacts and in series for Normally Closed contacts.