XR500 Series Programming Guide Digital Monitoring Products
11
CommuniCation
3.30
SPV/TRBL YES
Supervisory/Trouble Reports
This option displays when the Path Type is Primary. All backup paths within the group
follow the same programming for Supervisory/Trouble Reports. Default is Yes.
NO YES FIRE
When YES is selected, the following reports are sent for all zone types:
• Trouble • Low Battery • Missing • Fault
• Restorals • System Troubles • System Restoral
When FIRE is selected, the following reports are sent for Fire, Fire Verify, and Supervisory
Zones:
• Trouble • Low Battery • Missing • Fault
• Restorals • System Troubles • System Restoral
Serviceman reports are sent regardless of the selection made for Supervisory/Trouble
reports.
3.31
O/C USER NO YES
Opening/Closing and User Reports
This option displays when the Path Type is Primary. All backup paths within the group
follow the same programming for Opening/Closing and User Reports. Default is Yes.
When YES is selected, the following reports by user are sent to this receiver.
• Opening • Code changes (including adding, deleting, changing)
• Closing • Schedule changes (temporary, permanent, shift)
• Bypass • Holiday date changes
• Reset
3.32
DOOR ACS YES
Door Access Report
This option displays when the Path Type is Primary. All backup paths within the group
follow the same programming for Door Access Reports. Default is Deny.
NO YES DENY
Select YES to enable Door Access Granted and Denied reports to this receiver whenever
a door access is granted to a user. The Door Access Granted report is only sent if the
keypad number has also been selected in Access Keypads under the SYSTEM REPORTS
programming.
Select DENY to enable Door Access Denied reports only to this receiver when a door
access is denied to a user.
3.33
PANIC TST NO YES
Panic Test (XR500N/XR500E only)
YES allows the panic zone test verication and failure results to be sent to the central
station receiver. NO disables the panic test report. The default setting is NO. The system
test start, stop, panic zone verication, and panic zone failure messages sent to the
central station and the trips count operation are the same as used under the Walk Test.
See Using the Walk Test section in the Appendix.
3.34
SEND COMM TRBL:
Send Communication Trouble
NO YES
This option displays for each path and determines if and how communication trouble on
the path is sent to the receiver. A trouble message indicates both the path number and
communication type that failed. Default is Yes.
3.35
SEND PATH INFO:
Send Path Information
NO YES
This option displays for each path and if YES, each panel message includes path
information such as path number, communication type, and path type. Default is No.