Digital Monitoring Products XR500 Series Programming Guide
44
AreA InformAtIon
18.5
CLS CHK NO YES
Closing Check
Select YES to enable the panel to verify that all areas in the system are armed after
permanent or extended sched ules ex pire. If the Clos ing Check nds any areas disarmed
past the sched uled time, the keypads selected to display System Trouble Status displays
CLOSING TIME! and emits a steady beep. When Area Schedules is set to YES in Area
Information, the specic area and name display followed by — LATE.
When Auto Arm is NO, if within ten minutes the system is not armed or if the schedule
is not extended, a Late to Close report is sent to the SCS-1R Receiver. When Auto Arm is
YES, the area arms. See Automatic Arming section.
If the area becomes disarmed outside of any schedule, the Closing Check sequence
occurs after the Late Arm Delay time. See Late Arm Delay.
When Closing Check is NO and Auto Arm is YES, the system immediately arms when the
schedule expires. No warning tone occurs.
In addition, when Closing Check is NO, the option to extend a schedule does not display
when the schedule expires.
18.6
CLS CODE NO YES
Closing Code
When YES is selected, a code number is required for system arming. If NO is selected, a
code number is not required for system arming.
18.7
ANY BYPS NO YES
Any Bypass
When YES is selected, zones can be bypassed without a code number during the arming
sequence. A code number is always required to use the Bypass Zones option from the
menu.
18.8
AREA SCH NO YES
Area Schedules
Select YES to allow each area to set its own shift schedules 1 to 4. Enter NO to provide
one set of schedules for this system.
Note: Area Schedules are not designed to operate with All/Perimeter or Home/Sleep/
Away systems.
18.9
EARLY AMBUSH: 0
Early Morning Ambush (XR500N/XR500E only)
Enter the number of minutes (1 to 15) before a silent alarm (Early Morning Ambush S33) is
sent to the central station using the area 1 account number. Enter 0 (zero) to disable this
option.
When a user code is entered to disarm area 1 at a keypad or reader with Access
Areas assigned to area 1, the same or different user code must be entered within the
programmed number of minutes to prevent an ambush message from being sent to the
receiver. The second user code also must have authority to disarm area 1.
In addition, a zone activation with Alarm Action Message C also cancels the Early Morning
Ambush timer and stops an Ambush message from being sent to the receiver. See Report
to Transmit section in Zone Information.
The keypad does not display any indication that the ambush timer is running.
Indications can be provided by assigning an output number to Entry Out and Ambush Out
in Output Options. Entry Out turns on one minute before the timer expires and turns off
at expiration. Ambush Out turns on at the timers’ expiration and turns off when Sensor
reset is performed.
18.10
AREA NO: -
Area Number
Enter the number of the area to program. After entering the area number, press
COMMAND to enter the area name. Only Area systems allow the area name to be
changed.
Note: When All/Perimeter or Home/Sleep/Away is selected as the system type, the Area
Number does not display.
18.10.1
All/Perimeter Programming
When All/Perimeter is selected as the system type, program the Interior and Perimeter
areas as needed.
18.10.2
INT BDRM PERIM
Home/Sleep/Away Programming
When Home/Sleep/Away is selected as the system type, program the Interior, Bedroom,
and Perimeter areas as needed.
INT PERIM