Digital Monitoring Products XR500 Series Programming Guide
20
Device Setup
734 Site Code Programming
6.18.9 Site Code Position
Enter the site code start position in the data string. Press any top row Select key to enter
a number between 0-255. Default is 1.
6.18.10 Site Code Length
Enter the number of characters the site code contains. Press any top row Select key to
enter a number between 1-16. Default is 8.
6.18.11 User Code Position
Dene the User Code start bit position. Press any top row Select key to enter a number
between 0-255. Default is 9.
6.18.12 User Code Length
Dene the number of User Code bits. Press any top row Select key to enter
a custom number. On a 734 module, custom numbers can only be between 16-32.
On a 734N/734N-WiFi module, custom numbers can be between 1-255.
The default is 16.
6.18.13 Require Site Code
Press the top row Select key under YES to use a site code.
In addition to User Code verication, door access is only granted when any one site
code programmed at the SITE CODE ENTRY option matches the site code received in the
Wiegand string.
6.18.13.1 Site Code Display
734 Module: You can program up to 8 three-digit site codes. Site code range is
0-999. Any previously programmed site codes display. Dashes represent blank site
codes. Default is blank.
Note: A card with a site code greater than three digits cannot be used. Use
only cards with three-digit site codes.
734N/734N-WiFi Module: You can program up to 8 ve-digit site codes. Site
code range is 1-65535. Any previously programmed site codes display. Site Code
1 defaults to 127. Site Codes 2-8 default to blank. Dashes represent blank site
codes.
Site Code 1 displays rst. Enter a site code number followed by the Command
key to advance to the next option, Site Code 2. To delete an existing site code,
press any Select key. Either enter a new site code followed by Command, or
press Command to leave blank and continue to the next site code. Repeat these
steps to change, delete, or add up to 8 site codes.
6.18.14 Number of User Code Digits
The 734 module recognizes user codes from 4-10 digits in length. The 734N
/734N-WiFi
module recognizes user codes from 1-10 digits in length. Press any top row Select key to
enter a user code digit length. This number must match the user code number length
being used by the panel. Default is 5. For an XR500 Area System, use 4 to 10 digits
(typically 5). For all other systems and panels, use 4 digits.
Any selection above 5 digits require entry of the custom card denitions with custom site
and user code positions for the Wiegand string. When searching the bit string for the user
code, the digits are identied and read from left to right.
SITE CODE
POSITION: 1
SITE CODE
LENGTH: 8
USER CODE
POSITION: 9
USER CODE
LENGTH: 16
REQUIRE SITE
CODE? NO YES
SITE CODE 1: -
SITE CODE 1:
(1-65,535) 127
NO. OF USER CODE
DIGITS: 5