Digital Monitoring Products XR500 Series Programming Guide
2
IntroductIon
1.3 Encrypted Communications (XR500N/XR500E only)
Some installations require secure data communications. DMP offers NIST approved and UL Listed AES encrypted
communication. Use a unique passphrase to enable encrypted communications and provide a secure means for
data communications. See Network Options.
An XR500E panel communicates using AES encryption. If you currently have an XR500N panel installed, you may
purchase a separate feature key to activate encrypted communications using the Feature Upgrade process.
Encrypted communication cannot be enabled on a standard XR500 panel. For more information on the Feature
Upgrade process see Section 21 in this document.
1.4 Programmer Operation
There are 21 programming sections to choose from:
Programming Item Section in This Manual Programming Item Section in This Manual
Initialization 2 Output Information 12
Communication 3 Output Groups 13
Network Options 4 Menu Display 14
Messaging Setup 5 Status List 15
Device Setup 6 Printer Reports 16
Remote Options 7 PC Log Reports 17
System Reports 8 Area Information 18
System Options 9 Zone Information 19
Bell Options 10 Stop 20
Output Options 11 Set Lockout Code 21
Feature Upgrade 22
To choose a section for programming, press any top row Select key when the keypad displays the name of that
section. Sections 2 through 22 contain detailed instructions for each programming step.
1.5 Programmer Lockout Codes
The panel allows you to enter the programming function without entering a lockout code using steps 1 to 4
listed in Getting Started. We recommend, however, that you install a Lockout Code to restrict programming to
only those persons your company authorizes. You can do this by using the SET LOCKOUT CODE feature in the
Programmer. The Lockout Code restricts any unauthorized panel programming.
After resetting the panel and entering the code 6653, the keypad displays PROGRAMMER. Press COMMAND
to advance through the programming sections until SET LOCKOUT CODE displays (after STOP). Press any top
row Select key. The keypad displays ENTER CODE: – . Enter a 3 to 5 digit Programmer Lockout Code and press
COMMAND. The keypad displays ENTER AGAIN followed by ENTER CODE: –. Enter the same 3 to 5 digit code a
second time and press COMMAND. The keypad displays CODE CHANGED.
Note: The panel does not accept a 5-digit Lockout Code higher than 65535.
Before accessing programmer functions enter the new code number. Write the Lockout Code number down and
keep it in a secure place with access limited to authorized persons only. Lost Lockout Codes require the panel
to be sent back to DMP for repair. You may cancel a Lockout Code by entering 00000 at the Set Lockout Code
command.
1.6 Reset Timeout
The panel has a feature that requires you to enter the Programmer within 30 minutes of resetting the panel.
After 30 minutes, if you attempt to program by entering the 6653 (PROG) code, the keypad displays: RESET
PANEL. You must reset the panel and enter the program code then begin programming within the next 30
minutes.
If you are already in the Programmer and do not press any keys on the programming keypad for 30 minutes, the
panel terminates programming. All data entered up to that time is Not saved unless you run the Stop routine.
Note: Use the Stop routine to exit panel Programming. Ensure the keypad displays “SAVING PROGRAM” to save
all programming changes entered.
1.7 Power Up
When the XR500 Series panel is powered up after an AC power failure, any zone transitions are not recognized
for 60 seconds. Normal zone processing resumes at the end of the 60 seconds.