XR500 Series Programming Guide Digital Monitoring Products
5
IntroductIon
1.13 Multiple Displays
For many programming and user options, such as Area selections, Menu Displays, and Status Lists, there are
several displays containing programming. For example, when programming Menu Displays, keypads 1 through 16
display on two separate displays. First, keypads 1 through 8 display. Press the COMMAND key to display keypads
9 through 16. This same scheme is used for areas 1 through 32.
Note: Areas not pre-programmed at installation to display at this keypad cannot be viewed.
1.14 Asterisks in Programming
Asterisks display next to a programming option that is already selected. As shown in the example, options that
are selected to display the current programming selection have an asterisk next to the number. Those that are
not selected simply display the number. In the Devices example, keypads 3, 8, 9, and 15 are not selected. In
the Areas example, areas 3, 8, 9, 15, 19, 23, 25, and 31 are not selected. In both examples the numbers with
asterisks are selected.
*1 *2 3 *4
*5 *6 *7 8 *13 *14 15 *16
9 *10 *11 *12
Devices
*29 *30 31 *32
*13 *14 15 *16
9 *10 *11 *12
25 *26 *27 *28
*1 *2 3 *4
*5 *6 *7 8 *21 *22 23 *24
*17 *18 19 *20
Areas
To select or deselect a number, simply enter the number using the digit keys on the keypad. This same scheme
is used when viewing the panel armed status and other programming and operational functions. Remember to
press the COMMAND key to display the rest of the device or area numbers.
1.15 Compliance Instructions (ANSI/UL 864)
This product incorporates eld-programmable software. In order for the product to comply with the ANSI/ UL
864 requirements, certain programming features or options must be limited to specic values as indicated
below. Refer to the XR500 Installation Guide (LT-0681) for additional information.
Program feature or option Permitted in
UL 864?
Possible settings Settings permitted in UL
864
System Reports, RESTORAL Y NO, YES, DISARM YES, DISARM
System Options, PWR FAIL HRS Y 0, 1 - 15 1 – 3
System Options, RETARD DELAY for
Waterow Applications
Y 0, 1 - 250 1 – 90
Bell Options, FIRE TYPE Y STEADY, PULSED, TEMPORAL,
NONE
STEADY OR TEMPORAL
Status List, SYSTEM TROUBLES Y Any combination of 1 – 16
addresses
Any combination 1 – 16
addresses
Status List, FIRE TYPE Y Any combination of 1 – 16
addresses
Any combination 1 – 16
addresses
Zone Information, TRANSMITTER
SUPERVISION TIME for Model 1103
Y 0, 3, 60, 240 3
Zone Information, RETARD for
Smoke Detectors
N NO, YES NO