XR100 Series Programming Guide Digital Monitoring Products
55
Zone InformatIon
18.16
OUTPUT: NONE
Output Action
EnteringanOutputNumberdisplaysthisoption.Thisoptionallowsyoutoassignan
output action to the relay: Steady, Pulse, Momentary, or Follow.
STD PLS MOM FOLW
STEADY - The output is turned on and remains on until the area is disarmed, an
output cutoff time expires, or the output is reset from the keypad menu.
PULSE - The output alternates one second on and one second off. Note: The
pulsingrateforaModel716relayattachedtotheLX-Busis1.6seconds.
MOMENTARY - The output is turned on only once for one second.
FOLLOW - The output is turned on and remains on while the zone is in an off
normal, or bad condition. When the zone restores, the output is turned off.
Note:ForDayZonetypes,whenanoutputisturnedon,ausercodewithsilence
authority can turn the output off.
After you make the three selections in the sections above, the display prompts you
for the same three selections for Disarmed Short, Armed Open, and Armed Short
conditions.Ifthezoneisa24-hourtype,onlytheArmedOpenandArmedShort
conditions display. When you have programmed all of the zone conditions, the
Swinger Bypass selection then dis plays.
18.17
SWGR BYP NO YES
Swinger Bypass
SelectingYESallowsthezonetobeswingerbypassedbythepanelaccordingtothe
specicationsprogrammedinSwingerBypassTripsandResetSwingerBypass.The
BypassconditiondisplaysinthekeypadStatusList.SelectingNOdisablesswinger
bypassing for this zone.
How it works
Ifwithinonehour,azonetripsthetotalnumberoftimesASspeciedinSwinger
Bypass Trips, the panel bypasses it until the following conditions occur; the area
in which the zone is assigned is disarmed, the zone is manually reset through the
BypassZones?keypadUserMenufunction,thezoneremainsnormalforonehour
andtheResetSwingerBypassisYES.
Ifthezonetripsfewerthanthespeciedtimeswithinonehour,thebypasstrip
counterreturnsto0(zero)andtheprocessmustberepeated.
AreportoftheswingerbypassissenttothereceiverifBypassReportsisYES.
Note: Not investigated by UL.
18.18
PREWARN KEYPADS:
Prewarn Keypad Addresses
Attheentrydelaystart,allkeypadaddressesselectedheredisplayENTERCODE:-.
Ifyouwanttheprewarntosoundatall8addresses,leavethedefaultsetting.
To delete an address, press the matching number on the keypad. To disable
prewarning at all keypads, press a top row Select key to clear the addresses shown.
Press the COM MAND key when the address selection is com plete.
Theprewarntonestopsatthekeypadwheretherstusercodedigitisentered.If
nokeysarepressedforvesecondsoraninvalidusercodeisentered,theprewarn
tone resumes at that keypad.
18.19
ENTRY DELAY: 1
Entry Delay
Selecttheentrytimerforthiszone.Entrytimers1to4areprogrammedinSystem
Options.
18.20
RETARD NO YES
Zone Retard Delay
WhenyouselectYES,thezoneoperateswiththezoneretarddelay.Theretard
func tions only in zone short condi tions.
The zone must re main shorted for the full length of the re tard de lay before the
panel recognizes its condition. If you select NO, the zone operates without a retard
delay.
Note: For UL installations, Zone Retard Delay shall not be used for burglary zones.
18.21
PRESGNL KEYPADS:
Presignal Keypad Addresses
You can enable any combina tion of keypad addresses to sound a presignal tone
during the time a zone is in retard delay. The presignal tone si lences when the zone
restores or the re tard delay expires.
To en able a presignal ad dress, press any top row Select key followed by the number
ofthekeypadaddress.Youcanenablethepresignalforall8keypadaddresses.
To disable a presignal address press the matching number digit again. Press the
COMMAND key when the address selection is complete. The Presignal option is only
displayedwhenRetardisselectedasYES.