Digital Monitoring Products XR100 Series Programming Guide
54
Zone InformatIon
18.12
ALARM ACTION . . . .
Alarm Action
ThisoptionallowsyoutochangeanyZoneTypestandarddenitions.Whenthe
ZoneTypeisspecied,theAlarmActionforthatzoneisstoredinmemory.
IftheZoneTypeisBlank,Night,Day,Exit,Auxiliary1,orAuxiliary2itisa
non-24-hourzoneandtheAlarmActionprogramingbeginswithDisarmedOpen.
IftheZoneTypeisFire,Panic,Emergency,orSupervisoryitisa24-hourzonethat
is always armed and the Alarm Action programming begins with Armed Open.
TheFireVerifyZoneTypefunctionsthesameasFireType,withthefollowing
exceptions:WhenaFireVerifyzoneinitiatesanalarm,thepanelperformsa
SensorReset.IfanyFireVerifyzoneinitiatesanalarmwithin120secondsafterthe
reset,analarmisindicated.Ifanalarmisinitiatedafter120seconds,thecycleis
repeated and a zone fault report is sent to the receiver.
DoNOTprogramFireVerifyZoneTypesforZoneRetard.
18.13
DISARMED OPEN
Disarmed Open
Denestheactiontakenbythepanelwhenthezoneisopenedwhiletheareais
disarmed.Therearethreeactionstodene:Reporttotransmit,RelayOutputto
activate, and Relay Output action.
You must also make these selections for the Disarmed Short, Armed Open, and
Armed Short zone conditions. Press COMMAND to continue.
18.14
MSG: TROUBLE
Report to Transmit
PressanySelectkeytodisplaythefollowingreportoptions:A,T,L,S,and-(dash).
ALARM - Select A to send an alarm report to the receiver and activate the bell
output according to zone type. The zone name appears in the panel alarmed zones
and status lists.
TROUBLE - Select T to send a trouble report to the receiver. The zone name
appears in the panel alarmed zones and status lists.
Note: ULrequirementspreventtheAlarm(A)andTrouble(T)actionforFire(FI),
andFireVerify(FV)zonetypesfrombeingchanged.
LOCAL - WhenyouselectL,analarmreportisNOTsenttothereceiver.Thebell
output activates and the zone name appears in the panel alarmed zones and status
lists.
- (Dash) - Whenyouselecta–(dash),reportsareNOTsenttothereceiver.The
bell output does not activate and there is no display in the panel alarmed zones or
status list. Only the relay output selected in the next section operates.
D S
DOOR PROPPED-SelectingD allows the following operation: The time programmed
intoENTRYDLY4intheSystem Option section begins to count without displaying
on keypad. If the time expires and the zone has not returned to normal, the keypad
troublebuzzerstartsandCLOSETHEDOORappearsonthekeypadsprogrammed
intothePREWARNADDRESSsection.ThetimeprogrammedintoENTRYDLY4begins
to count down again internally. If the time expires a second time and the zone has
notreturnedtonormal,afaultreportissenttothereceiverandthezonename-
OPENmessagedisplaysonthekeypadsuntilacodeisentered.Thebelloutputdoes
not activate for the Door Propped operation.
SILENCE/RESET - SelectSwhenthezone(notFI,SV,orFV)isconnectedtoaDMP
Model303Silence/Resetswitch,thezonecanbeusedtosilencethealarmbelland
perform a sensor reset without using a keypad. A report is NOT sent to the receiver
except for the bell silence report.
18.15
OUTPUT NO: 0
Output Number
You can specify any of the Relay Outputs on the XR100 Series panel to be activated
byazonecondition(1to6,500to599ifModel716used,D1toD8,G1toG20).The
output can be activated regardless of the report to transmit or whether or not the
zone is programmed as local. An output activated by an armed zone is turned off
when the zone area is disarmed by a user.
To enter an output number, press a top row Select key followed by the output
number. Press the COMMAND key.