XR100 Series Programming Guide Digital Monitoring Products
39
StatuS LiSt
15.5
BURGLARY ZONES:
Burglary Zones
1 2 3 4
5 6 7 8
Speciesthekeypadaddresses(1through8)whereallburglaryzonealarmsand
troublesdisplay.BurglaryzonesincludeNight,Day,andExittypezones.Burglary
zone troubles remain in the list until the zone restores. All keypads are selected by
default.
For zone alarms, only the last burglary zone tripped re mains in the list. The alarm
re mains in the list un til another burglary zone goes into alarm, any area of the
system is dis armed. This ensures that if a bur glary is in progress the last zone
tripped remains in the list even if the zone is restored.
The keypad buzzer sounds for one second on bur glary alarms.
WhenusingLCDKeypads,thepanelprovidesdistinctspeakertonesfromthe
keypad for Burglary:
On - Burglary zone alarm and Bell Output or Burglary Bell Output is ON.
Off - Alarm Silence.
YoucanfurtherdenewhichkeypadaddressshowsaBurglaryZoneeventby
entering that area number in the Display Areas menu during Device Setup.
15.6
SPRVISORY ZONES:
Supervisory Zones
1 2 3 4
5 6 7 8
Speciesthekeypadaddresses(1through8)whereallsupervisoryzonealarms
and troubles display. Supervisory zones are entered in the sta tus list and sound the
keypad buzzer until a valid user code is entered at any keypad address. If a trouble
condition remains in the display, the buzzer sounds at 10:00 am daily until the
supervisorytroubleisclearedfromtheStatusList.
15.7
PANIC ZONES:
Panic Zones
1 2 3 4
5 6 7 8
Speciesthekeypadaddresses(1through8)whereallpaniczonealarmsand
troubles display. The name of the zone remains in the list until the zone re stores.
The keypad buzzer does not sound for panic alarms or troubles.
15.8
EMERGENCY ZONES:
Emergency Zones
1 2 3 4
5 6 7 8
Speciesthekeypadaddresses(1through8)whereallemergencyzonealarmsand
troubles display. The name of the zone remains in the list until the zone re stores.
The keypad buzzer does not sound for emer gency alarms or troubles.
15.9
AUX 1 ZONES:
Auxiliary 1 Zones
1 2 3 4
5 6 7 8
Speciesthekeypadaddresses(1through8)whereallAuxiliary1zonealarmsand
troubles display. The name of the zone remains in the list until the zone restores.
The keypad buzzer does not sound for Auxiliary 1 alarms or troubles.
YoucanfurtherdenewhichkeypadaddressshowsanAuxiliary1Zoneeventby
entering that area number in the Display Areas menu during Device Setup.
15.10
AUX 2 ZONES:
Auxiliary 2 Zones
1 2 3 4
5 6 7 8
Speciesthekeypadaddresses(1through8)whereallAuxiliary2zonealarmsand
troubles display. The name of the zone remains in the list until the zone restores.
ThekeypadbuzzerdoesnotsoundforAuxiliary2alarmsortroubles.
YoucanfurtherdenewhichkeypadaddressshowsanAuxiliary2Zoneeventby
entering that area number in the Display Areas menu during Device Setup.
15.11
COMM PATH TRBL:
ALL NO YES
Communication Trouble
Specieswhencommunicationtroublesaredisplayedonkeypadsthatare
programmed to display System Monitor Troubles. Default is NO.
SelectYEStodisplaycommunicationtroublewhenanycommunicationpathfails.
SelectALLtodisplaycommunicationtroubleonlywhenallpathshavefailed.
Comentarios a estos manuales