Digital Monitoring Products XR100 Series Programming Guide
8
CommuniCation
Communication
3.1
COMMUNICATION
Communication
Congurethecommunicationoptionsforthepanel.Theinformationyouprogram
varies with the Communication Type you select.
3.2
ACCOUNT NO: 12345
Account Number
The Account Number is a 1 to 5 digit number used to identify which panel is sending
amessage.EntertheaccountnumbersenttotheSCS-1RReceiver.Messagesmay
besenttoacentralstationorviaPCLogReportstoaPC.Thedefaultis12345.
NET, CELL, and DD -Therangeofvalidaccountnumbersforapanelis1to65535.
For accounts of four digits or less, do not enter leading zeros.
CID - Chooseanaccountnumberbetween1and9999.
3.3
XMIT DELAY: 30
Transmit Delay
Enterthenumberofseconds(15to45)thepanelwaitsbeforesendingburglary
zones(Night,Day,orExit)reportstothereceiver.Otherzonetypereportsare
sent immediately. Alarm bells and relay outputs are not delayed during this period.
ProgramBurglaryOutputsforpulsedorsteady,andsetAbortReportstoYESif
OpeningandClosingreportsarenotbeingsent.Enter0(zero)todisablethis
function.Thedefaultis30.
If the area where the alarm occurred is disarmed during the Transmit Delay time,
onlyanAbortReport(S45)messageissenttothereceiver.Iftheareawhere
the alarm occurred is disarmed after the alarm message is sent to the receiver
but before the Bell Cutoff time expires even if the alarm was silenced, an Alarm
Cancelled(S49)messageissent.Otherwisethealarmissentattheendofthe
delay. The Alarm Cancelled report cannot be disabled.
Note: For Commercial Burglary Installations, the combined Transmit Delay
(Abort Window) and Entry Delay must not exceed one (1) minute.
3.4
PATH: -
Communication Path
Uptoeightcommunicationpathsmaybeprogrammed.Eachpathisdesignatedas
a primary or backup communication route. Path 1 is always Primary but other paths
may be programmed as additional primary or backup.
Eachprimarypathestablishesanewpathgroup.Apathgroupismadeupofthe
primary path and its subsequent backup paths. Typical communication takes place
on the primary path with backup paths being used only when the primary path fails
or when the backup path is programmed to duplicate messages. There is no option
tobackuppath8.
3.5
COMM TYPE: DD
Communication Type
Speciesthecommunicationmethodthepanelusesonthispathtoreportsystem
eventstoDMPSCS-1RReceiversornon-DMPreceivers.DefaultisDDforPath1,and
NONEforPath2-8.
NONE - Forlocalsystems.SelectingNONEendscommunicationprogramming.
DD - DigitalDialercommunicationstoaDMPSCS-1RReceiver.
NET - Network communication using the panel onboard network connection. The
DMPNetwork/Outputreportingformatistransmittedoveradatanetworktothe
SCS-1RReceiver.
CID - Thisoptionallowsthepaneltocommunicatetonon-DMPreceiversusingthe
Contact ID format.
CELL - Thisoptionallowscommunicationoverthecellularnetworkusingthe463C,
464-263Cor464-263HCellularCommunicators.