XR100 Series Programming Guide Digital Monitoring Products
11
CommuniCation
3.20
PROTOCOL: TCP
Protocol
ThisoptiondisplaysonlywhenCommunicationTypeisNET.
SelectTCPtocommunicateoverthenetworkusingTCPprotocol.SelectUDPto
communicateusingUDPprotocol.DefaultisTCP.
3.21
RETRY SECONDS: 6
Retry Seconds
ThisoptiondisplaysforNETCommunicationTypes.
Enterthenumberofseconds(between6and15)thepanelshouldwaitbefore
retrying to send a message to the receiver if an acknowledgment was not received.
The panel retries as many times as possible for a period of one minute before
sending a network trouble message. For example, if retry time is set to 15, the
panelretriesfourtimes.ThedefaultRetryTimeis6seconds.
Note:IfTCPisenabled,theminimumRetryTimeprogrammedis6seconds.
3.22
SUB CODE NO
Substitution Code
ThisoptiondisplayswhentheCommunicationTypeisNET,orCELL.ThePanel
Substitution Code increases the level of security by helping to ensure that the
panel sending the message to the receiver has not been substituted by another
panel. The default is NO.
SelectYEStosendasubstitutioncodewitheverymessage.
SelectSHARED(SHR)tousethesamesubstitutioncodeasoperatingintheprevious
path.
3.23
893A: NO YES
893A
This option displays when the Communication Type is DD or CID.
The893AoptionallowsreportstobesenttothereceiveronasecondDDlineusing
the893Amodule.DefaultisNo.
Whenusingthisoption,TestReportmessages(S07AutomaticRecallTestorS88
UnrestoredSystemRecallTest)willbesenttothereceiveratthefrequency
programmedinTestFrequency,alternatingbetweentherstandsecondphone
line.
Forexample,aDDpathwithan893Amodulesetfordailytestreportfrequency
willsendatestreportthroughphoneline1onedayandphoneline2thenextday.
If893AoptionissettoYES,enteruptoa3digitprextobedialedbeforethe
secondphonenumber.Ifnoprexisentered,thesecondphonenumberisdialedas
originally entered.
3.24
ALARM SWITCH: 1
Alarm Switch
This option displays for DD or CID Communication Types.
Enterthenumberofattemptstosendanalarmmessagebeforeswitchingto
thenextpath.Rangeisfrom1to10.Allnon-alarmmessageswillbesentfor
10 attempts on the dialer before a switch is initiated. If the path immediately
following this channel is not a backup path, this option has no effect. Default is 1.
3.25
DUPLICATE ALARMS
Duplicate Alarms
ThisoptiondisplaysforBACKUPpaths.IfYesisselected,thecurrentbackuppath
duplicates all alarms occurring on its group primary path. Default is No.
3.26
ALARM YES
Alarm Reports
This option displays when the Path Type is Primary. All backup paths within the
group follow the same programming for Alarm Reports. Default is Yes.
NO YES FIRE
WhenYESisselected,thefollowingreportsaresenttothereceiverforallzone
types:
•Alarm •Bypass •Reset •Restore
WhenFIREisselected,thefollowingreportsaresentforFire,FireVerifyand
SupervisoryZones:
•Alarm •Bypass •Reset •Restore
NO YES SHARED
-