Digital Monitoring Products Canadian XR100 Guía de instalación Pagina 28

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 36
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 27
Digital Monitoring Products XR100 Series Canadian Installation Guide
22
ComplianCe
False Alarm Reduction Programmable Options *
24.1 Shipping Defaults and Recommended Programming for ANSI/SIA CP-01-2010
SIA CP-01 FEATURE
PARAGRAPH # AND
DESCRIPTION
DMP XR100 SERIES
PROGRAMMING
GUIDE LT-0896
SECTION #
REQUIREMENT RANGE
SHIPPING
DEFAULT
RECOMMENDED
PROGRAMMING*
4.2.2.1ExitTime 14.2ExitDelay
Required
(Programmable)
45sec.-250sec.
60
Seconds
60 Seconds
4.2.2.2Progress
Annunciation
14.2ExitDelay Allowed
Individual keypads
may be disabled per
zone
All
keypads
enabled
All keypads enabled
4.2.2.3ExitTime
Restart
14.2ExitDelay Required Option
For re-entry during
exit time
Enabled Enabled
4.2.2.5AutoStayArm
on Unvacated Premises
32.3 Occupied
Premise -
See XR100
SeriesProgramGuide
(LT-0896CAN)
Required Option
(except for
remote arming)
Area 1 = Perimeter
Area 2 = Interior
Enabled
Enabled for
Residential
Applications
4.2.4.4ExitTimeand
ProgressAnnunciation/
Disable - for Remote
Arm
Not Available on
Remote Arming
Allowed Option
Progress Annunciation
Always disabled for
Remote Arming
Not
Available
Remote Arming not
allowed for CP-01
installations.
4.2.3.1EntryDelay(s) 8.3 Entry Delay
Required
(Programmable)
30sec.–240Sec.**
30
Seconds
At least 30 Seconds **
4.2.5.1AbortWindow–
for Non-Fire Zones
3.7 Transmit Delay Required Option
Disable by zone or
zone type
Enabled
NT DY
EX Zone
Enabled
4.2.5.1AbortWindow
Time – for Non-Fire
Zones
3.7 Transmit Delay
Required
(Programmable
15sec.-45sec.**
30
Seconds
At least 15 Seconds **
4.2.5.1.2Abort
Annunciation
3.7 Transmit Delay Required Option
Annunciate that
no alarm was
transmitted(S45)
Yes Yes
4.2.5.4.1Cancel
Annunciation
Always Enabled - Not
Programmable
Required Option
Annunciate that
a Cancel was
transmitted(S49)
Always
Enabled
Yes
4.2.6.1&4.2.6.2
Duress Feature
User Code + 1 =
Ambush Code Not
Available
Allowed Option
No 1 + derivative of
anotherusercode/no
duplicates with other
user codes
Code +1
Always
Disabled
Not Programmable
4.3.1CrossZoning 15.21 Cross Zone Required Option
Yes/NoZone
Programming
No
Enabled using two or
more programmed
zones
4.3.1Programmable
Cross Zoning Time
8.4CrossZoneTime Allowed 4sec.-250sec. 4Seconds
Per walk path in
protected premises
4.3.2SwingerShutdown
8.7 Swinger Bypass
Trips
Required
(Programmable)
Forallnon-re
zones, shut down at
1 or 2 trips
One (1)
trip
One (1) trip
4.3.2SwingerShutdown
Disable
15.15 Swinger Bypass Allowed
For non-police
response zones
Yes Enabled (all zones)
4.3.3FireAlarm
Verication
15.4ZoneType Required Option FV Type Zone No
Yes as required
(unless sensors can
self verify)
4.5CallWaitingCancel
3.19 Telephone
Number
Required Option
Include*70Pin
Telephone Number
Disabled
Enabled if user has
call waiting
*ProgrammingatinstallationmaybesubordinatetootherULrequirementsfortheintendedapplication.
**Forlistedinstallations,combinedEntryDelayandTransmitDelayshouldnotexceed1minute.
Vista de pagina 27
1 2 ... 23 24 25 26 27 28 29 30 31 32 33 34 35 36

Comentarios a estos manuales

Sin comentarios