Listed Compliance Specications
19.1 Introduction
For applications that must conform to a local authorities installation standard or a National Recognized Testing Laboratory
certicatedsystem,pleaseseethefollowingsections.
Burglary Specications
20.1 Introduction
TheprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstallingtheXR100
SeriesCanadianpanelinaccordancewithanyoftheburglarystandards.Additionalspecicationsmayberequiredbya
particularstandard.SeetheXR100SeriesCanadianProgrammingGuide(LT-0896CAN).
20.2 Control Outside of Protected Area
APotterEVDorSentrol5402mustbeusedwhenthepanelisinstalledoutsideofthevaultinanancialapplication.Front
and rear tamper switches are required. Refer to the system wiring diagram.
20.3 Bypass Reports
The Bypass Reports option must be programmed as YES for all burglary applications.
20.4 System Maintenance
To ensure continuous satisfactory operation of any alarm system, proper installation and regular maintenance by
the installing alarm company and frequent testing by the end user is essential. Offering a maintenance program and
acquainting the user with the correct procedures for system use and testing is also the responsibility of the installing alarm
company.
ULC S304-06 Specications
Signal Receiving Center and Premise Burglar Alarm Control Units
21.1 For Low Risk Applications: Level A1
LevelA1communicationchannelsecurityisprovidedforInternet,Intranet,LANorWANnetworkswhenconguredasa
NET communicating system using the XR100N.
NET:
PRIMARY
SUB CODE: YES
CHECKINTIME: 2 MINUTES
FAIL TIME: 3 MINUTES
SEND COMM TRBL: YES
TCP COMM: YES
21.2 For Low Risk Applications: Level P1
LevelP1communicationchannelsecurityisprovidedwhenconguredasaDDcommunicatingsystemandadailytest
message using the XR100.
21.3 Dual Protection
For Medium or High Risk ULC Listed Applications: Use only zones 1-8 on the control panel and program Dual EOL as
Yes in panel programming. Program the Disarmed Short Message in Alarm Action of Zone Information programming as
a Trouble message.
Note:Ifusinga714,714-8,or714-16fordualprotection,programtwozonesasthesamenameorequivalentand
connect to the contact in the protected area as show in the Dual Zone Protection diagram in the back of this guide.
21.4 Remote Arming
For ULC Listed applications, remote arming is not permitted.
21.5 Zone Expansion
Use of the following zone expanders are permitted for connection of burglary devices:
710 Bus Splitter Module 714ZoneExpander,4zones 715ZoneExpander,4zones 7070(A)/7073(A)Keypads,4zones
711 Zone Expander, Single 714-8ZoneExpander,8zones 715-8 Zone Expander, 8 zones 7170/7173Keypads,4zones
712-8 Zone Expander, 8 714-16ZoneExpander,16zones 715-16 Zone Expander, 16 zones