XR150/XR350/XR550 Series Programming Guide Digital Monitoring Products
41
AREA INFORMATION
17.13 Automatic Arming
Select YES to allow this area to arm automatically according to permanent, temporary, or
extended schedules. If no schedules are programmed, the area auto arms every hour.
If closing check is selected as YES, the automatic arming function does not take place until
the expiration of a ten minute Closing Check delay. See Closing Check. If the area has been
disarmed outside of any permanent or temporary schedule, the closing check sequence
occurs one hour after the area is disarmed.
At arming, bad zones are handled according to the option selected in section Bad Zones.
If a closing report is sent, the user number is indicated as SCH on the SCS-1R Receiver. NO
disables automatic arming for this area.
Note: For ANSI/SIA CP-01 UL installations, Automatic Arming cannot be used for arming.
17.14 Bad Zones
At the time of automatic arming, some zones in the area may not be in a normal condition.
This option allows you to program the panel response to these bad zones. This option does
not display if AUTO ARM is NO.
BYP - All bad zones are bypassed. A report of the bypass is sent to the receiver if Bypass
Reports is YES. The report indicates SCH as the user number.
FORC - All bad zones are force armed. Zones force armed in a bad condition are capable
of restoring and reporting an alarm if tripped. A forced zone report is transmitted if Bypass
Reports is YES. The report indicates SCH as the user number.
REF - The automatic arming is refused and no arming takes place. A No Closing report is
sent to the receiver regardless of the Closing Check selection.
17.15 Automatic Disarming
NO disables automatic disarming by schedule for this area. When YES is selected, the area
automatically disarms according to permanent or temporary schedules. If an opening report
is sent to the receiver, the user number is indicated as SCH.
17.16 Armed Output Number
Enter the output to turn on when this area is armed. If an exit delay is used for this area,
the Armed Output turns on at the start of the exit delay. The output is turned off when
this area is disarmed. The output cannot be turned on from the User Menu Outputs On/Off
option.
17.17 Late Output Number
Enter the output to turn on when this area is not armed by its scheduled time and Area
Late or Closing Time displays at a keypad and the keypad buzzer is on. The output is turned
off when the keypad buzzer is silenced by pressing any key. Default is 0 (zero).
17.18 Late Arm Delay
Enter 4 to 250 minutes to delay before automatic re-arming occurs after the area becomes
disarmed outside of schedules. See Closing Check. Default is 60 minutes.
Note: The Late Arm Delay can be superseded by the Re Arm Delay setting of the User
Prole assigned to the user who disarmed the area. Refer to the Re Arm Delay section in
the XR150/XR350/XR550 Series User’s Guide (LT-1278).
17.19 Bank Safe & Vault (XR550 with Network or Encryption only)
NO disables the Bank Safe & Vault feature for this area. When selected as YES, schedules
set for any area and the time of day cannot be changed while the area is armed.
Program schedules before arming: A Bank Safe & Vault area can only be disarmed during
scheduled times. If the area becomes armed before programming a schedule, the panel
must be reset before the area can be disarmed from a keypad or the Bank Safe & Vault
option in Area Information must be set to NO.
Zones assigned to Bank Safe & Vault areas cannot be bypassed or force armed. Do not
assign Bank Safe & Vault area to an Arming zone. Arming zones can disarm Bank Safe &
Vault areas outside of a schedule.
17.20 Common Area
Select YES to enable this area to operate as a common area. This area is armed when
the last area in the system is armed and is disarmed when the rst area in the system is
disarmed. You can have multiple common areas in each system. For the common area to
work properly, do not assign the common area to any user code. When a user code can
arm and disarm the common area from a keypad at any time, the common area does not
function as a common area.
AUTO ARM NO YES
BAD ZONES: BYP
BYP FORC REF
AUTO DIS NO YES
ARMED OUTPUT: 0
LATE OUTPUT: 0
LATE/ARM DLY: 60
BANK/SAF NO YES
COMMON NO YES