Digital Monitoring Products XR150/XR350/XR550 Series Programming Guide
30
OUTPUT OPTIONS
Output Options
11.1 Output Options
This section allows you to program panel output options. The panel provides two Form
C relays (1 and 2) and four switched ground (open collector) outputs numbered 3 to 6.
Expand the system up to 500 additional relay outputs using any LX-Bus on the panel, or
multiple 716 Output Expander Modules. In addition, 45 wireless outputs are available
when using the 1100X Series wireless receiver. Refer to the XR150/XR350/XR550 Series
Installation Guide (LT-1233) for complete information.
Select from the following output numbers:
• 1 to 6
• 450 to 474
—
Slow response time* wireless outputs (activates within 15 seconds)
• 480 to 499 — Fast response time* wireless outputs (activates within 1 second)
• 500 to 999 — LX-Bus output, Relay output, Zone expansion output
• D1 to D16 — Keypad door strike relay for addresses 1-16
• F1 to F20 — To activate Z-Wave Favorites
• G1 to G20 — Output group
* The response time of a wireless output is the time it takes for a wireless output to
activate once the panel event occurs. You determine whether a wireless output is a slow
or fast response based on the output number assigned. A slow response output number
extends battery life, but response time may be up to 15 seconds. A fast response output
number responds within 1 second, but reduces battery life. Refer to the specic wireless
output installation guide to determine battery life.
11.2.1 Cutoff Output
Outputs 1 to 6 can be entered here to turn off after a time specied in CUTOFF TIME. To
disable this option, press any Select key to clear the display then press COMMAND. The
Cutoff Output displays dashes when no outputs are selected.
11.2.2 Output Cutoff Time
If a Cutoff Output (1-6) is assigned, enter a Cutoff Time of 1 to 99 minutes for the output
to remain on. Enter 0 (zero) for continuous output.
11.3 Communication Trouble Output
Enter the output/Favorite number to turn on when a DD system fails to communicate on
three successive dial attempts or if the backup communication line transmits a report.
The Communication Trouble Output also turns on when NET is selected as the primary
communication method and NET communication fails after one minute. When NET
communication is restored the Communication Trouble Output automatically turns off.
To manually turn the output off, disarm any area or select Off for the output number in the
User Menu Outputs On/Off section. Enter 0 (zero) to disable this output.
11.4 Fire Alarm Output
Enter the output/Favorite number to turn on when a re type zone is placed in alarm. The
output is turned off using the Sensor Reset option while no additional re type zones are in
alarm. Enter 0 (zero) to disable. This output is not compatible with Cutoff Outputs.
11.5 Fire Trouble Output
Enter the output number to turn on when a re type zone is placed in trouble, when a
supervisory type zone is placed in trouble, or when any system monitor (AC, Battery, Phone
Line 1 or Phone Line 2) is placed in trouble. The output turns off when all re and supervisory
type zones, or system monitors are restored to normal. Enter 0 (zero) to disable this output.
This output is not compatible with Cutoff Outputs. This output can be connected to a lamp,
LED, or buzzer using the DMP Model 716 Output Expansion Module.
11.6 Panic Alarm Output
Enter the output/Favorite number to turn on when any Panic type zone is placed in an
alarm condition. The output is turned off after all Panic zones are restored from an alarm
condition and a Sensor Reset is performed. Enter 0 (zero) to disable.
Wireless Outputs
• The Panic Alarm is compatible with the Model 1118 Wireless Remote Indicator Light
and the Model 1116 Wireless Relay Output connected to a Model 572 Indicator LED.
• When a Panic Alarm occurs, the LED turns on steady for ve minutes and then turns off.
• When a Panic Test is initiated from the keypad, the LED ashes quickly for ve minutes.
• For a Panic Alarm, a fast response wireless output number is recommended.
11.7 Ambush Output
Enter the output/Favorite number to turn on when an Ambush code is entered at a keypad.
The output is turned off using the Sensor Reset option. Enter 0 (zero) to disable.
OUTPUT OPTIONS
CO OUTS: - - - - - -
CUTOFF TIME: 0
COMM FAIL OUT: 0
FIRE ALR OUT: 0
FIRE TRB OUT: 0
PANIC ALM OUT: 0
AMBUSH OUT: 0