XR500 Series Canadian Installation Guide Digital Monitoring Products
23
ComplianCe
22.3 For Low Risk Applications: Level A1
LevelA1communicationchannelsecurityisprovidedforInternet,Intranet,LANorWANnetworkswhenconguredas
a NET communicating system using the XR500N.
22.4 For Low Risk Applications: Level P1
LevelP1communicationchannelsecurityisprovidedwhenconguredasaDDcommunicatingsystemandadailytest
message using the XR500.
22.5 Dual Protection
For Medium or High Risk ULC Listed Applications: Use only zones 1-8 on the control panel and program Dual EOL as
Yes in panel programming. Program the Disarmed Short Message in Alarm Action of Zone Information programming as
a Trouble message.
Ifusinga714,714-8,or714-16fordualprotection,programtwozonesasthesamenameorequivalentandconnect
to the contact in the protected area as show in the Dual Zone Protection diagram in the back of this guide.
22.6 Remote Arming
For ULC Listed applications, remote arming is not permitted.
22.7 Zone Expansion
Use of the following zone expanders are permitted for connection of burglary devices:
710 Bus Splitter Module 714ZoneExpander,4zones 715ZoneExpander,4zones 7070(A)/7073(A)Keypads,4zones
711 Zone Expander, Single 714-8ZoneExpander,8zones 715-8 Zone Expander, 8 zones 7170/7173Keypads,4zones
712-8 Zone Expander, 8 714-16ZoneExpander,16zones 715-16 Zone Expander, 16 zones
ULC S559-04 Specications
Equipment for Fire Signal Receiving Centers and Systems
23.1 For Fire Communicator Applications
Forrecommunicatorapplications,communicationtotheresignalreceivingcenterisprovidedforInternet,
Intranet,LANorWANnetworkswhenconguredasaNETorCELLcommunicatingsystemusingtheXR500Series
panel. See wiring diagram in section 26.5 for additional information. Program one of the following options in panel
Communication:
Path 1 Type NET or CELL Primary with no Backup
Path 1 Programming
Comm Type = NET or CELL Checkin Min = 3
Path Type = Primary Failtime Min = 3
Sub Code = No Send Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
Path 1 Type NET Primary and Path 2 Type CELL Backup
Path 1 Programming Path 2 Programming
Comm Type = NET Comm Type = CELL
Path Type = Primary Path Type = Backup
Test Rpt = Yes Test Rpt = Yes
Test Freq = 1 Dy Test Freq = 1 Dy
Send Comm Trbl = Yes Send Comm Trbl = Yes
Comm Path Trbl = Yes (Status List Programming)
23.2 Central Station Host Automation
Theresignalreceivingcenter’shostautomationsystemmustrecognizethefollowingsignals:Zone1Alarm=Fire
Alarm,Zone2Trouble=FireZoneTrouble,Zone3Trouble=ACTrouble,Zone4Trouble=BatteryTrouble,andZone
5Trouble=GroundFaultTrouble.