Digital Monitoring Products XR500 Series Canadian Installation Guide
22
ComplianCe
Listed Compliance Specications
20.1 Introduction
For applications that must conform to a local authorities installation standard or a National Recognized Testing
Laboratorycerticatedsystem,pleaseseethefollowingsections.
Burglary Specications
21.1 Introduction
Theprogrammingandinstallationspecicationscontainedinthissectionmustbecompletedwheninstallingthe
XR500SeriesCanadianpanelinaccordancewithanyoftheburglarystandards.Additionalspecicationsmaybe
requiredbyaparticularstandard.SeetheXR500SeriesCanadianProgrammingGuide(LT-0679CAN).
21.2 Control Outside of Protected Area
APotterEVDorSentrol5402mustbeusedwhenthepanelisinstalledoutsideofthevaultinanancialapplication.
Front and rear tamper switches are required. Refer to the system wiring diagram.
21.3 Bypass Reports
The Bypass Reports option must be programmed as YES for all listed burglary applications.
21.4 System Maintenance
To ensure continuous satisfactory operation of any alarm system, proper installation and regular maintenance by
the installing alarm company and frequent testing by the end user is essential. Offering a maintenance program and
acquainting the user with the correct procedures for system use and testing is also the responsibility of the installing
alarm company.
ULC S304-06 Specications
Signal Receiving Center and Premise Burglar Alarm Control Units
22.1 For Medium or High Risk Applications: Level A3 Communication
LevelA3communicationchannelsecurityisprovidedforInternet,Intranet,LANorWANnetworkswhencongured
as a NET or CELL communicating system using the XR500E. The following options must be programmed in XR500E
Canadian panel Communication:
NET PRIMARY CELL PRIMARY:
SUB CODE: YES SUB CODE: YES
CHECKINTIME: 2 MINUTES CHECKINTIME: 3 MINUTES
FAIL TIME: 3 MINUTES FAIL TIME: 3 MINUTES
SEND COMM TRBL: YES SEND COMM TRBL: YES
TCP COMM: YES ENCRYPTION: ENABLED
ENCRYPTION: ENABLED
22.2 For Very High Risk Applications: Level A3 Plus P1 Communication
Additionally, XR500E communicating system may use two channels (NET plus Dialer, CELL plus Dialer, or NET plus CELL)
to send signals simultaneously. The following options must be programmed in XR500E Canadian panel Communication:
NET PRIMARY DIALER PRIMARY:
SUB CODE: YES USE DAILY TEST
CHECKINTIME: 2 MINUTES
FAIL TIME: 3 MINUTES
SEND COMM TRBL: YES
TCP COMM: YES
ENCRYPTION: ENABLED
CELL PRIMARY DIALER PRIMARY:
SUB CODE: YES USE DAILY TEST
CHECKINTIME: 3 MINUTES
FAIL TIME: 3 MINUTES
SEND COMM TRBL: YES
ENCRYPTION: ENABLED
NET PRIMARY CELL PRIMARY:
SUB CODE: YES YES
CHECKINTIME: 2 MINUTES or less 24HOURSorless
FAIL TIME: 3 MINUTES or less
SEND COMM TRBL: YES
TCP COMM: YES
ENCRYPTION: ENABLED
Inaddition,theSCS-104NetworkLineCardinstalledintheSCS-1RReceivermusthavetheACKSubstitutionMessage
programmed as NO.