Installation
XRSuper6/XR20/XR40 Installation Guide
15
2500 N. Partnership Boulevard Springfield, MO 65803 www.dmpnet.com Digital Monitoring Products
UL 1635 SPECIFICATIONS
Digital Burglar Alarm Communicator System Units
18.1 Digital Dialer telephone number
Both programmed telephone numbers must begin with a D or P. See the XRSuper6/XR20/XR40 Programming
Guide (LT-0305).
18.2 Entry delay
The maximum entry delay used must not be more than 60 seconds. See the XRSuper6/XR20/XR40 Programming
Guide (LT-0305).
18.3 Exit delay
The maximum exit delay used must not be more than 60 seconds. See the XRSuper6/XR20/XR40 Programming
Guide (LT-0305).
18.4 Test frequency
The Test Frequency option must be programmed so that the panel sends a report once every 24 hours. See the
XRSuper6/XR20/XR40 Programming Guide (LT-0305).
18.5 Automatic bell test
This option must be programmed as YES. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
18.6 Grade B Central Station
Grade B Central Station service can be provided under UL 1635 by adding a Grade A local audible signal appliance
and placing the Model XRSuper6/XR20/XR40 panel into the Model 350A Grade A Attack Resistant Housing.
UL 365 and 609 SPECIFICATIONS
Police Station Connected and Local Burglar Alarm Units and Systems
19.1 Entry delay
The maximum entry delay used must not be more than 60 seconds when using the Model 349A Grade A housing.
See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
19.2 Grade A bell
A Grade A local audible signal appliance must be used.
19.3 Bell cutoff
The bell cutoff time cannot be less than 15 minutes. See the XRSuper6/XR20/XR40 Programming Guide (LT-0305).
19.4 Automatic bell test
The Automatic Bell Test option must be programmed as YES. See the XRSuper6/XR20/XR40 Programming Guide
(LT-0305).
19.5 Grade A Mercantile
For Grade A Mercantile and Police Station Connect operation the Model XRSuper6/XR20/XR40 must be mounted
in a Grade A attack resistant housing, (DMP Model 350A).
19.6 Mercantile Safe and Vault
When the DMP Model 350A housing is used, the panel provides operation as a mercantile safe and vault alarm.
Bell Supervision and wiring must be in accordance- with UL 681. If the panel is mounted outside the safe or
vault, tamper protection and the Sentrol Model 5402 or Potter EVD listed vibration detectors should be used. The
XRSuper6/XR20/XR40 does not provide operation as a Bank Safe and vault alarm.
19.7 Line security for Police Connect
Basic line security is provided when the Model XRSuper6/XR20/XR40 is configured as a dialer system.