NOtIFICAtION CIRCuIt
EXPANSION
Easily add NAC outputsto the XR150FC/
XR550FCsystem.UptothreeClassBmodules
canbemountedwithintheFACP.Model865or
866ClassBNACModulesmaybecombined
withapowersupplytoprovideadditional4
Amp NACoutputs. Use an 867 on the SLC
LooptofurtherexpandNACcircuits.
FIRE DRILL AND ONE-MAN
wALk tESt
Users can test firenotification bells using
theFireDrillfeature.Aspecialcodeisalso
availableforinstallerstotestthesystem.The
one-man walk test featureallows a single
technician to check the panel response to
fire,burglary,panicandsupervisoryzones.
buILt-IN PROgRAMMER
AND DIAgNOStICS
Noprogrammingdeviceisrequired,enabling
installers and service technicians to fully
programthesystemandrundiagnosticsfrom
anyDMPLCDkeypad.Checktheelectrical
stateofzones,findindividualzonenumbers,
checkthe LX-Bus forMissing, Overlapping
and/orExtrazones,andmuchmore,allfrom
anyDMPLCDkeypad.
FLASh uPDAtEAbLE
TheXR150FC and XR550FC panels accept
softwareupdates from a remotelocation
usingRemoteLink™software.Whennew
XR150FC/XR550FCfeatureupdatesrelease,
performtheflashupdateremotely.
OutPutS
TheXR150FC and XR550FC allowthe use
of two SPDT relay outputs and four open
collector outputs, that may be activated by
zoneorsystemevents,byschedule,through
theUserMenuorwhenacardispresented.
Output Groupsallow multiple outputs to
activate with a single eventand/or can be
assignedtoaparticularuserprofile.
OutPut SChEDuLES
Achievemaximum system flexibility with
100 programmable schedules that simplify
planning and operations. Control any
contact-activateddevicewithschedulesthat
automaticallyregulaterelaysandswitched-
groundoutputs.
MuLtI-LINguAL DISPLAyS
Foradditionalflexibility,keypadsattachedto
theXR150FCandXR550FCpanelscandisplay
keypadStatusListandUserMenutextusing
multiplelanguages.Theuserhastheoption
toselectthelanguagetouse.
StAtuS LISt
Toprovidemaximum system flexibility, fire
zones maybe programmedto display at a
specifickeypad.Inthismanner,allfirezones
canbemonitoredinonelocationandother
zonescanbeprogrammedtodisplayandbe
monitoredatdifferentkeypadlocations.
12,000 EvENt MEMORy
Allows the user to view the last 10,000
door accesses or 2,000 system events that
occurredoverthepast45days.
REMOtE LINk
TheRemote Link programming software
takesadvantageoftheeasy-to-usesimplicity
ofMicrosoft
®
Windows™.TheXR150FCand
XR550FCincludeaninterfaceconnectionfor
installerstousetoconnectalaptopcomputer.
EIght COMMuNICAtION PAthS
Create,configure,and manage up to eight
communicationpathsbetweenthepaneland
CentralStation.Eachpathhasitsownpanel
communication programmingparameters,
and can be identified as either primary or
backup.Thisenablesinstallerstoconfigurea
reliablecommunicationlink,offeringgreater
confidence that the panel will alwaysbe
connectedtotheCentralStation.
COMMuNICAtION FuNCtION
DIAgNOStICS
Theenhanced diagnostic menu enables
technicians to check network and cellular
communicationstatus,cellsignalstrength,
andemailstatusfromthekeypad.
FIRE ZONE PROgRAMMINg
Programzonesforfire,fireverify,fireretard,
presignal,crosszoning,orfiresupervisory.
Thisflexibility allows the ability to match
individualzonecharacteristicstotheneeds
ofanyareainthefireinstallation.
ZONE EXPANSION
TheXR150FCandXR550FCprovideupto570
zones, programmablefor a variety of fire
applications. The system providesClass B
12VDCpowered zones,two on-board and
four on the 715 Module, plus eight panel
burglaryzones.Upto60zonesareavailable
on15keypadaddressesandupto100zones
areavailableoneachbuilt-inLX-Bus™using
ExpansionModules.
FIRE vERIFy
Usedprimarilyforsmokedetectorcircuitsto
verifytheexistenceofanactualfirecondition.
Whena FireVerifyzoneinitiates analarm,
the panel performs a Sensor Reset. If any
FireVerifyzoneinitiatesanalarmwithin120
secondsafterthereset,analarmisindicated.
If an alarm is initiatedafter another 120
seconds,thecycleisrepeated.